Contract award record
PR4070 - Ventilation Services Remediation Works-Mortuary
Notice details
- Published
- Category
- works
- Buyer region
- London
- Source
- View official notice
Public buyer and contract winner
Award value£43,452
- AwardedCompleted
- StartCompleted
- EndCompleted
Work description
The existing Air Handling serving the Mortuary is located within the plant room within the loft space of the stand alone Mortuary Building. It is understood that during a recent validation test, the Mortuary was found to be under a positive air pressure. HTM 03-01 Appendix 2.0 indicates that Post Mortem rooms should be maintained under a negative pressure, (Supply air 10 air changes per hour; Extract 12 air changes per hour). In order to satisfy this requirement,